Report
DHI-2026-0148

Property Inspection Report

42 Fictional Crescent

Ottawa, Ontario, K2G 0X0

Front elevation
Prepared forSample Client
Inspection date2026-03-14
Inspected by[Inspector name]
On site09:00 – 12:45
(343) 209-6235 · book@doctorhomeinspector.com · doctorhomeinspector.com
Performed to the InterNACHI Residential Standards of Practice

How to read this report

Every finding is written the same way — what was observed, why it matters, and what to do about it — and carries one of five ratings. The ratings describe urgency and consequence, not cost.

Safety hazardA condition that poses a risk of injury, fire, or carbon monoxide exposure. Address before occupancy.8 items
Major concernA significant defect, an item at the end of its service life, or a condition likely to require substantial expense.8 items
Repair / replaceA defect that should be corrected by a qualified trade, but is neither dangerous nor unusually expensive.10 items
MonitorNot a defect today. A condition worth watching, or routine maintenance that has fallen behind.4 items
ImproveThe component works and met the standard when built. An upgrade would improve safety, comfort, or efficiency.1 item
No repair costs appear in this report.

This report deliberately contains no repair cost estimates. Real figures depend on the contractor, the season, access, and the scope you choose, and a number written here would anchor your expectations to something that is not a quote. Take the items in the summary to licensed trades and get written quotes.

What was inspected

This inspection was a non-invasive, visual examination of the readily accessible systems and components of the property, performed on the date shown, and designed to identify material defects observed at that time.

What this inspection is not

The property, and the day

Conditions on the day of an inspection determine what can be seen. Snow cover, a shut-off utility, or an occupied basement all limit what any inspector can report, so they are recorded here.

Property typeDetached house
Approximate year built1974
Approximate size1,850 sq ft
Storeys2
Bedrooms / bathrooms4 / 2.5
Foundation typeConcrete block
Front of house facesSouth-west
OccupancyOccupied — furnished
WeatherOvercast
Outdoor temperature4 °C
Ground conditionsDamp
Utilities on at time of inspectionAll utilities on
Present during inspectionClient, client's agent
Client's agentSample Agent, Sample Realty
Limitations that applied on this inspection

Stored belongings along the north and east basement walls limited access to approximately 30 percent of the foundation. The area beneath the deck was not accessible. Snow remained on the north roof slope and that area was assessed from the ground and from the attic only.

Summary of findings

This summary lists the conditions the inspector considered most significant. It is a navigational aid, not a substitute for the report. Items not listed here may still require attention, and the full report contains information about every system that was inspected. Read the whole document before you waive a condition.

8Safety
8Major
10Repair
4Monitor
1Improve

Safety hazard8

1

Guard height below current standard

Exterior › Decks, porches & balconies · Rear deck, 34 inches measured

Safety hazard

Observation. The guard is lower than the 36-inch minimum required for residential decks.

Why it matters. A low guard is a fall hazard, particularly with children.

Recommendation. Have the guard raised to current code height.

2

Garage door auto-reverse not functioning

Exterior › Garage

Safety hazard

Observation. The garage door's automatic reverse did not operate correctly on test.

Why it matters. This is the safety feature that stops the door from closing on a person or a child. It must reverse on contact and on beam interruption.

Recommendation. Have the opener serviced or replaced and both reverse mechanisms verified.

3

TPR discharge pipe missing or improper

Plumbing › Water heater

Safety hazard

Observation. The temperature and pressure relief valve discharge pipe is missing, terminates too high, is undersized, or is threaded at the end.

Why it matters. The TPR valve is the device preventing a water heater from becoming an explosive vessel. An improper discharge line can scald an occupant, or the threaded end invites someone to cap it.

Recommendation. Have a plumber install a proper full-size discharge line terminating within 6 inches of the floor, unthreaded.

4

No GFCI protection near water

Electrical › Receptacles, switches & GFCI/AFCI · Both bathrooms, garage, exterior

Safety hazard

Observation. Receptacles within the required distance of a sink, or in the bathroom, kitchen, garage, unfinished basement or exterior, are not GFCI protected.

Why it matters. GFCI protection is the difference between a shock and an electrocution when a person is near water. It is the highest-value, lowest-cost electrical correction in most homes.

Recommendation. Have a licensed electrician install GFCI protection at all required locations.

5

No carbon monoxide alarm with fuel-burning appliance

Electrical › Smoke & carbon monoxide alarms

Safety hazard

Observation. No carbon monoxide alarm was found, in a home with a fuel-burning appliance or an attached garage.

Why it matters. Ontario law requires a carbon monoxide alarm adjacent to sleeping areas in homes with a fuel-burning appliance or an attached garage. Carbon monoxide has no smell and the symptoms are mistaken for flu.

Recommendation. Install CO alarms adjacent to all sleeping areas immediately.

6

Handrail missing or not graspable

Interior, Doors & Windows › Stairs & railings — interior · Basement stairway

Safety hazard

Observation. The stairway lacks a handrail, or the handrail is not graspable.

Why it matters. Stairs are where people fall in houses, and a graspable handrail is what stops the fall.

Recommendation. Install a continuous graspable handrail meeting current standards.

7

Range not anti-tip secured

Interior, Doors & Windows › Appliances (where included)

Safety hazard

Observation. The freestanding range does not have an anti-tip bracket installed.

Why it matters. A range can tip forward when weight is applied to an open door, which is a serious hazard around children.

Recommendation. Install the manufacturer's anti-tip bracket.

8

Dryer vent restricted with lint

Interior, Doors & Windows › Appliances (where included)

Safety hazard

Observation. The dryer vent duct is restricted with lint accumulation.

Why it matters. Restricted dryer venting is a documented and common cause of house fires, and it lengthens every drying cycle.

Recommendation. Have the duct cleaned and establish an annual cleaning schedule.

Major concern8

9

Granular loss — advanced wear

Roof › Roof covering · South and west slopes

Major concern

Observation. The shingles show widespread granular loss, with the asphalt mat exposed in places. Granules are the shingle's protection against ultraviolet light; once they are gone the mat degrades quickly.

Why it matters. The covering is at or near the end of its serviceable life and should be budgeted for replacement rather than repair.

Recommendation. Obtain quotes for full roof replacement. Budget accordingly as part of your purchase planning.

10

Negative grade — slopes toward foundation

Exterior › Grading & site drainage · North elevation

Major concern

Observation. The grade slopes toward the foundation on one or more sides of the house.

Why it matters. Surface water is directed at the foundation instead of away from it. Along with downspout discharge, this is the leading cause of basement water entry, and it is far cheaper to correct outside than to manage inside.

Recommendation. Regrade to fall a minimum of 6 inches over the first 10 feet away from the foundation.

11

No flashing at the ledger

Exterior › Decks, porches & balconies

Major concern

Observation. No flashing was observed where the deck ledger meets the house.

Why it matters. Water runs behind the ledger into the rim joist, which rots out of sight and eventually destroys the connection holding the deck to the house.

Recommendation. Have proper ledger flashing installed.

12

Equipment beyond typical service life

Heating › Heating equipment

Major concern

Observation. The heating equipment is beyond the typical service life for its type. It operated at the time of inspection.

Why it matters. Age alone is not a defect, but a furnace past 20 years should be budgeted as a near-term replacement. Failures happen in January, at the worst possible cost and inconvenience.

Recommendation. Budget for replacement. Have an HVAC contractor perform a full service and combustion analysis.

13

Polybutylene (Poly-B) supply piping

Plumbing › Water supply piping

Major concernInsurance

Observation. The supply piping is polybutylene, commonly installed between roughly 1978 and 1998.

Why it matters. Poly-B degrades from the inside where it contacts chlorinated water and fails without warning, typically at the fittings. Ontario insurers will not write a policy on a home with Poly-B, or will exclude water damage entirely.

Recommendation. Confirm insurability with your broker before waiving conditions, and obtain quotes for full repiping.

Inspector's note. Grey Poly-B was observed at the water heater and in the basement ceiling. Copper is present at the fixtures, suggesting a partial replacement. The extent behind finished walls could not be established.

14

Aluminum branch circuit wiring

Electrical › Branch wiring

Major concernInsurance

Observation. Aluminum branch circuit wiring was observed. It was installed primarily between 1965 and 1976.

Why it matters. Aluminum expands and contracts more than copper and oxidises at terminations, and loose connections overheat. Ontario insurers commonly require a certificate from a licensed electrician confirming the terminations have been remediated, or they decline the risk.

Recommendation. Have a licensed electrician (ECRA/ESA) inspect all terminations and remediate with approved connectors such as AlumiConn or COPALUM. Obtain the certificate for your insurer.

Inspector's note. Aluminum branch wiring was observed at several receptacles on the main floor. No remediation connectors were visible at the devices sampled.

15

Bathroom exhaust terminates in the attic

Attic, Insulation & Ventilation › Attic ventilation & moisture · Main bathroom fan

Major concern

Observation. A bathroom exhaust fan discharges into the attic rather than to the exterior.

Why it matters. This delivers a continuous stream of warm, wet air directly into the coldest part of the building. It is one of the most common causes of attic mould in cold-climate homes.

Recommendation. Have the duct extended to a proper exterior roof or wall termination, insulated along its run, and sealed.

16

Frost or condensation on sheathing

Attic, Insulation & Ventilation › Attic ventilation & moisture

Major concern

Observation. Frost or condensation staining was observed on the underside of the roof sheathing.

Why it matters. This confirms warm moist air is reaching the attic. Left uncorrected it degrades the sheathing and grows mould.

Recommendation. Air-seal the attic floor — around light fixtures, the hatch, plumbing stacks, and top plates — then correct the ventilation.

Repair / replace10

17

Evidence of ice damming

Roof › Roof covering · North eave above the garage

Repair / replace

Observation. Staining and deterioration at the eaves are consistent with ice damming in previous winters.

Why it matters. Ice damming forces meltwater backwards under the shingles and into the wall and ceiling assemblies. In a cold climate it is a symptom of heat loss into the attic and inadequate ventilation, not of the roof covering itself.

Recommendation. Improve attic insulation and ventilation, seal attic air leaks, and verify ice-and-water membrane extends at least 3 feet up-slope from the interior wall line at the next re-roof.

18

Plumbing vent boot cracked

Roof › Flashings

Repair / replace

Observation. The rubber boot on one or more plumbing vent stacks is cracked and has lost flexibility.

Why it matters. This is one of the most common causes of ceiling stains. The boots are inexpensive and easily replaced.

Recommendation. Replace the vent boots.

19

Downspouts discharge at the foundation

Roof › Eavestroughs & downspouts · North-east and south-west corners

Repair / replace

Observation. One or more downspouts discharge directly at the foundation wall rather than being extended away from the house.

Why it matters. This is the single most common cause of wet basements. A roof sheds thousands of litres per storm, and delivering that volume against the foundation saturates the soil, loads the foundation wall, and finds any crack that exists.

Recommendation. Extend all downspouts a minimum of 6 feet from the foundation, discharging onto grade that slopes away.

20

Staining at the base of the foundation wall

Structure & Foundation › Water intrusion evidence · North-east corner

Repair / replace

Observation. Staining and mineral deposits were observed at the base of the foundation wall, indicating past water entry.

Why it matters. Basement water is nearly always an exterior drainage problem. It recurs seasonally, usually during spring melt and heavy summer storms.

Recommendation. Correct downspout extensions and grading first. Re-evaluate after one full wet season.

Inspector's note. This is directly below the downspout reported under Roof. Correct the downspout and the grading before considering any interior work — in this order, and re-evaluate after one full spring melt.

21

No backup power for sump pump

Structure & Foundation › Sump pump & drainage

Repair / replace

Observation. The sump pump has no battery backup or water-powered backup.

Why it matters. The heaviest rain events come with the wind and the outages that accompany them. A sump pump without backup fails at exactly the moment it is needed most.

Recommendation. Install a battery backup sump system.

22

Water heater beyond typical service life

Plumbing › Water heater

Repair / replace

Observation. The water heater is beyond typical service life. It was functional at the time of inspection.

Why it matters. Tanks fail by leaking, not by stopping. A tank failure in a finished basement causes significant damage.

Recommendation. Budget for replacement, and consider a leak alarm or automatic shutoff valve.

23

Tub or shower surround sealant failed

Plumbing › Fixtures & faucets · Main bathroom

Repair / replace

Observation. The sealant at the tub or shower surround has failed.

Why it matters. Water enters the wall behind the surround, where it rots the framing and the subfloor.

Recommendation. Remove the failed sealant and re-caulk with a mould-resistant sanitary sealant.

24

Laundry — no shutoff valves or hoses beyond life

Plumbing › Fixtures & faucets

Repair / replace

Observation. The laundry connections lack accessible shutoffs, or the supply hoses are rubber and beyond their service life.

Why it matters. A burst washing machine hose is one of the most common causes of major household water damage.

Recommendation. Install quarter-turn shutoffs and replace rubber hoses with braided stainless steel.

25

Double-tapped breaker

Electrical › Service & main panel · Positions 12 and 14

Repair / replace

Observation. Two conductors were observed terminated under a single breaker not rated for it.

Why it matters. The terminal cannot clamp both conductors reliably. The loose one arcs, and arcing inside a panel is how panel fires start.

Recommendation. Have a licensed electrician separate the conductors onto their own breakers.

26

Attic hatch not insulated or weatherstripped

Attic, Insulation & Ventilation › Insulation

Repair / replace

Observation. The attic hatch is uninsulated and not weatherstripped.

Why it matters. The hatch is a direct hole in the thermal envelope. Warm moist air rises through it into the attic and condenses.

Recommendation. Insulate the hatch to the level of the surrounding attic and weatherstrip the perimeter.

Monitor4

27

Efflorescence on foundation wall

Structure & Foundation › Foundation walls · North wall, below grade

Monitor

Observation. White mineral deposits (efflorescence) were observed on the interior foundation wall.

Why it matters. Efflorescence is left behind when water moves through the masonry and evaporates. It confirms moisture is passing through the wall, though not necessarily that it is a current problem.

Recommendation. Address exterior drainage first — downspouts and grading — and monitor.

28

Heat exchanger not fully visible — inspection limited

Heating › Heating equipment

Monitor

Observation. The heat exchanger could not be fully viewed. Complete evaluation of a heat exchanger requires dismantling the unit, which is beyond the scope of a home inspection.

Why it matters. A cracked heat exchanger releases combustion products, including carbon monoxide, into the airstream. It cannot be ruled out by visual inspection alone.

Recommendation. Have a licensed HVAC technician perform a combustion analysis and heat exchanger evaluation.

29

Not tested — outdoor temperature too low

Cooling › Cooling equipment

Monitor

Observation. The cooling system was not operated because the outdoor temperature was below 15°C. Running an air conditioner in cold weather can damage the compressor.

Why it matters. The system's cooling performance is therefore unverified.

Recommendation. Have the system evaluated by an HVAC contractor at the start of the cooling season.

30

Failed thermal seal — fogging between panes

Interior, Doors & Windows › Windows · Two second-floor bedroom windows

Monitor

Observation. Fogging between the panes was observed in one or more windows, indicating seal failure.

Why it matters. The unit has lost most of its insulating value. It is a comfort and efficiency issue rather than a defect that must be corrected.

Recommendation. Individual glazing units can be replaced without replacing the whole window.

Improve1

31

Insulation below current standard

Attic, Insulation & Ventilation › Insulation

Improve

Observation. The attic insulation depth is materially below the current standard for this climate zone. Ontario's Building Code calls for approximately R-60 in new attic construction.

Why it matters. Under-insulated attics cost money every heating season and are a primary driver of ice damming. Topping up an attic is one of the highest-return improvements available on an older home.

Recommendation. Air-seal the attic floor first, then top up the insulation. Check for national and utility efficiency rebates in your area.

Inspector's note. Depth measured between 5 and 7 inches, roughly R-18 to R-25 against a current standard of approximately R-60.

Items your insurer will ask about

The items on this page are conditions that Ontario insurers commonly refuse, surcharge, or require remediation for before binding a policy. This is not an insurance determination — only your insurer or broker can make one — but these are the conditions that most often derail a closing after the financing is in place. Send this page to your broker as early as you can.

1

Polybutylene (Poly-B) supply piping

Plumbing › Water supply piping

Major concernInsurance

Observation. The supply piping is polybutylene, commonly installed between roughly 1978 and 1998.

Why it matters. Poly-B degrades from the inside where it contacts chlorinated water and fails without warning, typically at the fittings. Ontario insurers will not write a policy on a home with Poly-B, or will exclude water damage entirely.

Recommendation. Confirm insurability with your broker before waiving conditions, and obtain quotes for full repiping.

Inspector's note. Grey Poly-B was observed at the water heater and in the basement ceiling. Copper is present at the fixtures, suggesting a partial replacement. The extent behind finished walls could not be established.

2

Aluminum branch circuit wiring

Electrical › Branch wiring

Major concernInsurance

Observation. Aluminum branch circuit wiring was observed. It was installed primarily between 1965 and 1976.

Why it matters. Aluminum expands and contracts more than copper and oxidises at terminations, and loose connections overheat. Ontario insurers commonly require a certificate from a licensed electrician confirming the terminations have been remediated, or they decline the risk.

Recommendation. Have a licensed electrician (ECRA/ESA) inspect all terminations and remediate with approved connectors such as AlumiConn or COPALUM. Obtain the certificate for your insurer.

Inspector's note. Aluminum branch wiring was observed at several receptacles on the main floor. No remediation connectors were visible at the devices sampled.

Roof

Roof covering

Deficient

Roof covering: Asphalt shingle. Inspected from: Ladder at the eaves. Layers: One. Estimated age: 15–20 yrs.

·

Granular loss — advanced wear

Roof › Roof covering · South and west slopes

Major concern

Observation. The shingles show widespread granular loss, with the asphalt mat exposed in places. Granules are the shingle's protection against ultraviolet light; once they are gone the mat degrades quickly.

Why it matters. The covering is at or near the end of its serviceable life and should be budgeted for replacement rather than repair.

Recommendation. Obtain quotes for full roof replacement. Budget accordingly as part of your purchase planning.

·

Evidence of ice damming

Roof › Roof covering · North eave above the garage

Repair / replace

Observation. Staining and deterioration at the eaves are consistent with ice damming in previous winters.

Why it matters. Ice damming forces meltwater backwards under the shingles and into the wall and ceiling assemblies. In a cold climate it is a symptom of heat loss into the attic and inadequate ventilation, not of the roof covering itself.

Recommendation. Improve attic insulation and ventilation, seal attic air leaks, and verify ice-and-water membrane extends at least 3 feet up-slope from the interior wall line at the next re-roof.

Flashings

Deficient

Flashings: Aluminum.

·

Plumbing vent boot cracked

Roof › Flashings

Repair / replace

Observation. The rubber boot on one or more plumbing vent stacks is cracked and has lost flexibility.

Why it matters. This is one of the most common causes of ceiling stains. The boots are inexpensive and easily replaced.

Recommendation. Replace the vent boots.

Eavestroughs & downspouts

Deficient

Eavestroughs & downspouts: Aluminum.

·

Downspouts discharge at the foundation

Roof › Eavestroughs & downspouts · North-east and south-west corners

Repair / replace

Observation. One or more downspouts discharge directly at the foundation wall rather than being extended away from the house.

Why it matters. This is the single most common cause of wet basements. A roof sheds thousands of litres per storm, and delivering that volume against the foundation saturates the soil, loads the foundation wall, and finds any crack that exists.

Recommendation. Extend all downspouts a minimum of 6 feet from the foundation, discharging onto grade that slopes away.

Soffits & fascia

Inspected

Inspected. No material deficiency observed.

Skylights & roof penetrations

Inspected

Inspected. No material deficiency observed.

Chimney — exterior

Inspected

Inspected. No material deficiency observed.

Exterior

Wall cladding

Inspected

Inspected. No material deficiency observed.

Grading & site drainage

Deficient

Grading & site drainage: Flat at foundation.

·

Negative grade — slopes toward foundation

Exterior › Grading & site drainage · North elevation

Major concern

Observation. The grade slopes toward the foundation on one or more sides of the house.

Why it matters. Surface water is directed at the foundation instead of away from it. Along with downspout discharge, this is the leading cause of basement water entry, and it is far cheaper to correct outside than to manage inside.

Recommendation. Regrade to fall a minimum of 6 inches over the first 10 feet away from the foundation.

Decks, porches & balconies

Deficient

Decks, porches & balconies: Pressure-treated wood.

·

No flashing at the ledger

Exterior › Decks, porches & balconies

Major concern

Observation. No flashing was observed where the deck ledger meets the house.

Why it matters. Water runs behind the ledger into the rim joist, which rots out of sight and eventually destroys the connection holding the deck to the house.

Recommendation. Have proper ledger flashing installed.

·

Guard height below current standard

Exterior › Decks, porches & balconies · Rear deck, 34 inches measured

Safety hazard

Observation. The guard is lower than the 36-inch minimum required for residential decks.

Why it matters. A low guard is a fall hazard, particularly with children.

Recommendation. Have the guard raised to current code height.

Walkways, driveway & steps

Inspected

Inspected. No material deficiency observed.

Garage

Deficient

Garage: Attached.

·

Garage door auto-reverse not functioning

Exterior › Garage

Safety hazard

Observation. The garage door's automatic reverse did not operate correctly on test.

Why it matters. This is the safety feature that stops the door from closing on a person or a child. It must reverse on contact and on beam interruption.

Recommendation. Have the opener serviced or replaced and both reverse mechanisms verified.

Exterior receptacles & lighting

Inspected

Inspected. No material deficiency observed.

Structure & Foundation

Foundation walls

Limited

Foundation walls: Concrete block. Visibility: Partly finished.

Limitation. Access was blocked by stored personal belongings.

·

Efflorescence on foundation wall

Structure & Foundation › Foundation walls · North wall, below grade

Monitor

Observation. White mineral deposits (efflorescence) were observed on the interior foundation wall.

Why it matters. Efflorescence is left behind when water moves through the masonry and evaporates. It confirms moisture is passing through the wall, though not necessarily that it is a current problem.

Recommendation. Address exterior drainage first — downspouts and grading — and monitor.

Water intrusion evidence

Deficient

Water intrusion evidence: Historical staining.

·

Staining at the base of the foundation wall

Structure & Foundation › Water intrusion evidence · North-east corner

Repair / replace

Observation. Staining and mineral deposits were observed at the base of the foundation wall, indicating past water entry.

Why it matters. Basement water is nearly always an exterior drainage problem. It recurs seasonally, usually during spring melt and heavy summer storms.

Recommendation. Correct downspout extensions and grading first. Re-evaluate after one full wet season.

Inspector's note. This is directly below the downspout reported under Roof. Correct the downspout and the grading before considering any interior work — in this order, and re-evaluate after one full spring melt.

Sump pump & drainage

Deficient

Sump pump & drainage: Sump pump present.

·

No backup power for sump pump

Structure & Foundation › Sump pump & drainage

Repair / replace

Observation. The sump pump has no battery backup or water-powered backup.

Why it matters. The heaviest rain events come with the wind and the outages that accompany them. A sump pump without backup fails at exactly the moment it is needed most.

Recommendation. Install a battery backup sump system.

Framing — floors, beams, columns

Inspected

Inspected. No material deficiency observed.

Crawlspace

Inspected

Inspected. No material deficiency observed.

Heating

Heating equipment

Deficient

Heating equipment: Forced-air furnace — natural gas. Approx. age: 15–20 yrs. Operated: Operated by thermostat — responded. Type: Mid-efficiency.

·

Equipment beyond typical service life

Heating › Heating equipment

Major concern

Observation. The heating equipment is beyond the typical service life for its type. It operated at the time of inspection.

Why it matters. Age alone is not a defect, but a furnace past 20 years should be budgeted as a near-term replacement. Failures happen in January, at the worst possible cost and inconvenience.

Recommendation. Budget for replacement. Have an HVAC contractor perform a full service and combustion analysis.

·

Heat exchanger not fully visible — inspection limited

Heating › Heating equipment

Monitor

Observation. The heat exchanger could not be fully viewed. Complete evaluation of a heat exchanger requires dismantling the unit, which is beyond the scope of a home inspection.

Why it matters. A cracked heat exchanger releases combustion products, including carbon monoxide, into the airstream. It cannot be ruled out by visual inspection alone.

Recommendation. Have a licensed HVAC technician perform a combustion analysis and heat exchanger evaluation.

Venting & flue

Inspected

Inspected. No material deficiency observed.

Heat distribution

Inspected

Inspected. No material deficiency observed.

Oil tank (if present)

Inspected

Inspected. No material deficiency observed.

Cooling

Cooling equipment

Not inspected

Cooling equipment: Central air — split system. Approx. age: 10–15 yrs. Operated: Not operated — outdoor temperature below 15°C.

Limitation. Seasonal shutdown — operating the equipment could damage it.

·

Not tested — outdoor temperature too low

Cooling › Cooling equipment

Monitor

Observation. The cooling system was not operated because the outdoor temperature was below 15°C. Running an air conditioner in cold weather can damage the compressor.

Why it matters. The system's cooling performance is therefore unverified.

Recommendation. Have the system evaluated by an HVAC contractor at the start of the cooling season.

Plumbing

Water supply piping

Deficient

Water supply piping: Polybutylene (Poly-B), Copper. Water source: Municipal. Main shutoff: Located and functional in appearance.

·

Polybutylene (Poly-B) supply piping

Plumbing › Water supply piping

Major concernInsurance

Observation. The supply piping is polybutylene, commonly installed between roughly 1978 and 1998.

Why it matters. Poly-B degrades from the inside where it contacts chlorinated water and fails without warning, typically at the fittings. Ontario insurers will not write a policy on a home with Poly-B, or will exclude water damage entirely.

Recommendation. Confirm insurability with your broker before waiving conditions, and obtain quotes for full repiping.

Inspector's note. Grey Poly-B was observed at the water heater and in the basement ceiling. Copper is present at the fixtures, suggesting a partial replacement. The extent behind finished walls could not be established.

Water heater

Deficient

Water heater: Natural gas tank. Approx. age: 12+ yrs. Ownership: Appears rented.

·

TPR discharge pipe missing or improper

Plumbing › Water heater

Safety hazard

Observation. The temperature and pressure relief valve discharge pipe is missing, terminates too high, is undersized, or is threaded at the end.

Why it matters. The TPR valve is the device preventing a water heater from becoming an explosive vessel. An improper discharge line can scald an occupant, or the threaded end invites someone to cap it.

Recommendation. Have a plumber install a proper full-size discharge line terminating within 6 inches of the floor, unthreaded.

·

Water heater beyond typical service life

Plumbing › Water heater

Repair / replace

Observation. The water heater is beyond typical service life. It was functional at the time of inspection.

Why it matters. Tanks fail by leaking, not by stopping. A tank failure in a finished basement causes significant damage.

Recommendation. Budget for replacement, and consider a leak alarm or automatic shutoff valve.

Drain, waste & vent

Inspected

Inspected. No material deficiency observed.

Fixtures & faucets

Deficient

Fixtures & faucets: Original to the home.

·

Tub or shower surround sealant failed

Plumbing › Fixtures & faucets · Main bathroom

Repair / replace

Observation. The sealant at the tub or shower surround has failed.

Why it matters. Water enters the wall behind the surround, where it rots the framing and the subfloor.

Recommendation. Remove the failed sealant and re-caulk with a mould-resistant sanitary sealant.

·

Laundry — no shutoff valves or hoses beyond life

Plumbing › Fixtures & faucets

Repair / replace

Observation. The laundry connections lack accessible shutoffs, or the supply hoses are rubber and beyond their service life.

Why it matters. A burst washing machine hose is one of the most common causes of major household water damage.

Recommendation. Install quarter-turn shutoffs and replace rubber hoses with braided stainless steel.

Electrical

Service & main panel

Deficient

Service & main panel: Overhead service, Breakers. Service size: 100 amp. Panel make: Federal Pioneer. Panel cover: Removed and inspected.

·

Double-tapped breaker

Electrical › Service & main panel · Positions 12 and 14

Repair / replace

Observation. Two conductors were observed terminated under a single breaker not rated for it.

Why it matters. The terminal cannot clamp both conductors reliably. The loose one arcs, and arcing inside a panel is how panel fires start.

Recommendation. Have a licensed electrician separate the conductors onto their own breakers.

Branch wiring

Deficient

Branch wiring: Copper NMD (Loomex), Aluminum branch wiring.

·

Aluminum branch circuit wiring

Electrical › Branch wiring

Major concernInsurance

Observation. Aluminum branch circuit wiring was observed. It was installed primarily between 1965 and 1976.

Why it matters. Aluminum expands and contracts more than copper and oxidises at terminations, and loose connections overheat. Ontario insurers commonly require a certificate from a licensed electrician confirming the terminations have been remediated, or they decline the risk.

Recommendation. Have a licensed electrician (ECRA/ESA) inspect all terminations and remediate with approved connectors such as AlumiConn or COPALUM. Obtain the certificate for your insurer.

Inspector's note. Aluminum branch wiring was observed at several receptacles on the main floor. No remediation connectors were visible at the devices sampled.

Receptacles, switches & GFCI/AFCI

Deficient

Receptacles, switches & GFCI/AFCI: Grounded three-prong, Ungrounded two-prong.

·

No GFCI protection near water

Electrical › Receptacles, switches & GFCI/AFCI · Both bathrooms, garage, exterior

Safety hazard

Observation. Receptacles within the required distance of a sink, or in the bathroom, kitchen, garage, unfinished basement or exterior, are not GFCI protected.

Why it matters. GFCI protection is the difference between a shock and an electrocution when a person is near water. It is the highest-value, lowest-cost electrical correction in most homes.

Recommendation. Have a licensed electrician install GFCI protection at all required locations.

Smoke & carbon monoxide alarms

Deficient

Smoke & carbon monoxide alarms: Battery only.

·

No carbon monoxide alarm with fuel-burning appliance

Electrical › Smoke & carbon monoxide alarms

Safety hazard

Observation. No carbon monoxide alarm was found, in a home with a fuel-burning appliance or an attached garage.

Why it matters. Ontario law requires a carbon monoxide alarm adjacent to sleeping areas in homes with a fuel-burning appliance or an attached garage. Carbon monoxide has no smell and the symptoms are mistaken for flu.

Recommendation. Install CO alarms adjacent to all sleeping areas immediately.

Fireplace & Solid Fuel

Fireplace / stove

Not present

Fireplace / stove: None present.

Attic, Insulation & Ventilation

Insulation

Deficient

Insulation: Blown cellulose. Approx. depth: 4–8". Attic access: Entered and traversed.

·

Insulation below current standard

Attic, Insulation & Ventilation › Insulation

Improve

Observation. The attic insulation depth is materially below the current standard for this climate zone. Ontario's Building Code calls for approximately R-60 in new attic construction.

Why it matters. Under-insulated attics cost money every heating season and are a primary driver of ice damming. Topping up an attic is one of the highest-return improvements available on an older home.

Recommendation. Air-seal the attic floor first, then top up the insulation. Check for national and utility efficiency rebates in your area.

Inspector's note. Depth measured between 5 and 7 inches, roughly R-18 to R-25 against a current standard of approximately R-60.

·

Attic hatch not insulated or weatherstripped

Attic, Insulation & Ventilation › Insulation

Repair / replace

Observation. The attic hatch is uninsulated and not weatherstripped.

Why it matters. The hatch is a direct hole in the thermal envelope. Warm moist air rises through it into the attic and condenses.

Recommendation. Insulate the hatch to the level of the surrounding attic and weatherstrip the perimeter.

Attic ventilation & moisture

Deficient

Attic ventilation & moisture: Soffit and roof vents.

·

Bathroom exhaust terminates in the attic

Attic, Insulation & Ventilation › Attic ventilation & moisture · Main bathroom fan

Major concern

Observation. A bathroom exhaust fan discharges into the attic rather than to the exterior.

Why it matters. This delivers a continuous stream of warm, wet air directly into the coldest part of the building. It is one of the most common causes of attic mould in cold-climate homes.

Recommendation. Have the duct extended to a proper exterior roof or wall termination, insulated along its run, and sealed.

·

Frost or condensation on sheathing

Attic, Insulation & Ventilation › Attic ventilation & moisture

Major concern

Observation. Frost or condensation staining was observed on the underside of the roof sheathing.

Why it matters. This confirms warm moist air is reaching the attic. Left uncorrected it degrades the sheathing and grows mould.

Recommendation. Air-seal the attic floor — around light fixtures, the hatch, plumbing stacks, and top plates — then correct the ventilation.

Roof structure (from attic)

Inspected

Inspected. No material deficiency observed.

Interior, Doors & Windows

Walls, ceilings & floors

Inspected

Inspected. No material deficiency observed.

Windows

Deficient

Windows: Double-glazed wood.

·

Failed thermal seal — fogging between panes

Interior, Doors & Windows › Windows · Two second-floor bedroom windows

Monitor

Observation. Fogging between the panes was observed in one or more windows, indicating seal failure.

Why it matters. The unit has lost most of its insulating value. It is a comfort and efficiency issue rather than a defect that must be corrected.

Recommendation. Individual glazing units can be replaced without replacing the whole window.

Doors

Inspected

Inspected. No material deficiency observed.

Stairs & railings — interior

Deficient

Stairs & railings — interior: Carpeted.

·

Handrail missing or not graspable

Interior, Doors & Windows › Stairs & railings — interior · Basement stairway

Safety hazard

Observation. The stairway lacks a handrail, or the handrail is not graspable.

Why it matters. Stairs are where people fall in houses, and a graspable handrail is what stops the fall.

Recommendation. Install a continuous graspable handrail meeting current standards.

Ventilation & indoor air

Inspected

Inspected. No material deficiency observed.

Appliances (where included)

Deficient

Appliances (where included): Range, Dishwasher, Washer, Dryer.

·

Range not anti-tip secured

Interior, Doors & Windows › Appliances (where included)

Safety hazard

Observation. The freestanding range does not have an anti-tip bracket installed.

Why it matters. A range can tip forward when weight is applied to an open door, which is a serious hazard around children.

Recommendation. Install the manufacturer's anti-tip bracket.

·

Dryer vent restricted with lint

Interior, Doors & Windows › Appliances (where included)

Safety hazard

Observation. The dryer vent duct is restricted with lint accumulation.

Why it matters. Restricted dryer venting is a documented and common cause of house fires, and it lengthens every drying cycle.

Recommendation. Have the duct cleaned and establish an annual cleaning schedule.

Ancillary service · included

Thermal Imaging

How this was done

Infrared imaging was performed with a thermal imager across the building envelope, ceilings below the attic, exterior walls, below-grade walls, visible plumbing runs, and the electrical panel. Infrared shows surface temperature differences only. It does not see through walls, and it does not detect moisture directly — anomalies are interpreted alongside moisture meter readings and visual observation.

Imager usedFLIR One Pro
Indoor/outdoor differential10–20°C — good
Areas scannedExterior walls, Ceilings below attic, Below-grade walls, Around all windows and doors, Electrical panel, Visible plumbing runs, Under all sinks
Anomalies foundInsulation gaps / thermal bridging
Moisture meter used to confirmYes
Findings and interpretationThermal anomalies consistent with missing or displaced insulation were imaged along the rear wall of the second-floor bedrooms and at the attic hatch. Moisture meter readings at these locations were normal, so these are thermal rather than moisture findings. A cold signature at the base of the north basement wall returned an elevated moisture reading and is reported under Structure.

Limitations of this service

Ancillary service · C-NRPP

Radon Measurement

How this was done

Radon measurement was conducted in the lowest lived-in level of the home, in the normal breathing zone, at least 50 cm from exterior walls and 20 cm from other objects, away from drafts, heat, and humidity, following Health Canada's Guide for Radon Measurements in Residential Dwellings.

The standard it is measured against. Health Canada sets the guideline for radon in indoor air in a dwelling at 200 Bq/m³, averaged over a minimum three-month period, and recommends remedial action above that level. The World Health Organization's reference level is lower, at 100 Bq/m³.

247 Bq/m³At or above Health Canada's guideline of 200 Bq/m³. Health Canada recommends remedial action. Sub-slab depressurisation typically reduces levels by 80 to 90 percent.
Measurement typeShort-term continuous monitor — 48+ hrs (real estate screening)
Device / kit IDRadonEye RD200 — unit 8841
Placement locationFinished basement — lived in
Placement descriptionBasement family room, 1.2 m above floor, 60 cm from the north wall, away from the return air grille
Deployed2026-03-12
Retrieved2026-03-14
Total exposure hours52
Closed-house conditions maintainedYes
Result (Bq/m³)247
Analysing laboratoryContinuous monitor — on-site analysis
Notes / conditions during the test periodClosed-house conditions were requested and appear to have been maintained. The basement is finished and used daily as living space, which is why it was selected as the measurement location.

Limitations of this service

Limitations & exclusions

Every home inspection has boundaries. These are ours, stated plainly, so there is no argument later about what was and was not included.

Concealed and inaccessible areas
Anything behind finished surfaces, under floor coverings, inside walls, buried, or otherwise not visible without dismantling or damaging the property. Inspectors do not move heavy furniture, lift carpet, or open finished assemblies.
Latent and hidden defects
Defects with no visible symptom on the day of the inspection cannot be found by a visual inspection and are outside its scope.
Life expectancy and future performance
No prediction is offered as to how long any component will continue to function. Any age estimate is an approximation based on observed condition and available data plates.
Cost estimates
Repair figures are not provided. Costs vary widely by contractor, scope, and season, and quoting them would be a disservice. Obtain written quotes from licensed trades.
Environmental hazards
Asbestos, lead, mould, radon, formaldehyde, PCBs, soil contamination, electromagnetic fields, and water quality are excluded unless a specific ancillary service was purchased and appears in this report as its own section.
Wood-destroying organisms
Identifying, quantifying, or treating termites, carpenter ants, or other wood-destroying organisms requires a licensed pest professional.
Systems shut down or seasonally off
Equipment that was shut off, disconnected, or seasonally out of service was not operated. Operating equipment outside its design conditions can damage it.
Below-grade and buried components
Underground tanks, septic components below grade, buried drainage, wells below the casing, and site services are outside the visual scope.
Detached structures and site elements
Sheds, fences, pools, spas, irrigation, playground equipment, and retaining walls are excluded unless specifically noted as inspected.
Cosmetic condition
Paint, wallpaper, finish quality, minor blemishes, and decorating are not defects and are not reported.
Adequacy of design
Whether a system was properly sized or well designed is an engineering question outside this inspection.
Recalls
Manufacturer recalls on appliances and components are not researched.

Inspection agreement

The terms agreed before the inspection began. They are reproduced in full because a term you have not read is a term you cannot rely on.

  1. Scope of the inspection. The Inspector will perform a non-invasive, visual inspection of the readily accessible systems and components of the property in accordance with the InterNACHI Residential Standards of Practice, which forms part of this Agreement and is available at https://www.nachi.org/sop.htm. The Client acknowledges having had the opportunity to read the Standards of Practice before the inspection.
  2. What the inspection is not. The inspection is not technically exhaustive. It is not a code compliance inspection, an appraisal, an environmental assessment, a pest inspection, or a warranty or guarantee of any kind, express or implied, on the condition or future performance of the property or any component of it.
  3. Non-invasive inspection. The Inspector will not dismantle equipment, remove finishes, move stored belongings or heavy furniture, or perform any act that risks damaging the property. Components that are concealed, buried, or not readily accessible will not be inspected, and the report will say so.
  4. Ancillary services. Radon measurement, solid fuel appliance inspection, sewer scope, well and septic inspection, and indoor air quality sampling are separate services outside the Standards of Practice. Where purchased, each is governed by its own stated protocol and limitations set out in the report, and each is limited to that scope.
  5. Report is for the Client. The report is prepared solely for the Client named in it and is not transferable. It reflects conditions on the date of the inspection only. Conditions change. The Inspector accepts no responsibility to any third party who obtains or relies on the report, and no responsibility for conditions arising after the date of inspection.
  6. Client's obligation to read the report. The Client agrees to read the entire report, including this Agreement, the scope, the limitations, and every section, before waiving any condition or completing any transaction. The summary is a convenience and does not replace the body of the report.
  7. Notice of claim and re-inspection. If the Client believes a condition was missed or misreported, the Client shall notify the Inspector in writing within fourteen (14) days of discovery and before the condition is repaired, altered, or disturbed. The Client shall allow the Inspector to re-inspect. Repairing or disturbing the condition before the Inspector has had that opportunity removes the Inspector's ability to assess the claim and releases the Inspector from liability for it.
  8. Limitation of liability. The Inspector's liability arising out of this inspection, whether in contract, tort, or otherwise, is limited to the fee paid for the inspection. The Client acknowledges that the fee is set on the basis of this limitation, that a home inspection is a limited visual service and not a warranty, and that a service without this limitation would carry a materially higher fee. The Client accepts this allocation of risk as a term of the Agreement.
  9. No consequential damages. Neither party is liable to the other for indirect, incidental, or consequential damages, including loss of use, loss of profit, or costs of accommodation.
  10. Payment. Payment is due on completion of the inspection unless otherwise agreed in writing. The report is released on receipt of payment.
  11. Governing law. This Agreement is governed by the laws of the Province of Ontario, and the parties submit to the jurisdiction of its courts.
  12. Entire agreement. This Agreement, together with the report and the Standards of Practice, is the entire agreement between the parties, and supersedes any prior discussion or representation. It may only be amended in writing signed by both parties.
Client
Sample ClientMarch 14, 2026 at 08:52
Inspector
[Inspector name]2026-03-14

Your inspector

[Inspector name]

Certified Professional Inspector

  • InterNACHI Certified Professional Inspector® (CPI) · No. [cert no.]

$2,000,000 general liability · $1,000,000 errors & omissions. Certificates available on request.

Call us. There is no time limit on that.

Questions about anything in this report, this week or three years from now, go to (343) 209-6235 or book@doctorhomeinspector.com. There is no charge and no expiry — this is how we would want it done for our own family, and it is why people send us their friends.